8 Rockwell Automation Publication 750-TD001H-EN-P - June 2013
PowerFlex 750-Series AC Drives
Vibration - Operating
Vibration - Packaged for Shipment
Sinusoidal Loose Load:
Random Secured:
Frames 1…2:
Frames 3…5:
Frames 6…7:
Frames 8…10:
Frames 1…5:
Frames 6…10:
Frames 1…5:
Frames 6…10:
1.000 mm (0.040 in.) displacement, 2 g peak
1.000 mm (0.040 in.) displacement, 1.5 g peak
1.000 mm (0.040 in.) displacement, 1 g peak
Power Core, Drive in Cabinet w/Option Bay - 1.000 mm (0.040 in.) displacement, 1 g peak
20.0 mm (0.8 in.) peak to peak, 2…5.186 Hz; 1.1 g peak from 5.186…20 Hz
Meets ISTA 2B packaging standards
Frequency (Hz)
PSD (g
2
/Hz)
1 0.00005
40.01
16 0.01
40 0.001
80 0.001
200 0.00001
Meets International Safe Transit Association (ISTA) test procedure 2B
Required Airflow: Frame
1…2
3
4
5
6
Total Fan Air Flow
0.024 CMS (50 CFM)
0.038 CMS (80 CFM)
0.151 CMS (320 CFM)
0.245 CMS (520 CFM)
0.238 CMS (504CFM)
Frame
7
8
9
10
Total Fan Air Flow
0.357 CMS (756 CFM)
0.637 CMS (1350 CFM)
1.274 CMS (2700 CFM)
1.911 CMS (4050 CFM)
Sound: Frame
1…2
3
4
5
6
Sound Level
63 dB
64 dB
72 dB
77 dB
73 dB
Frame
7
8
9
10
Sound Level
74 dB
79 dB
79 dB
83 dB
Note: Sound pressure level is
measured at 2 meters.
Surrounding Environment Pollution Degree
Pollution Degree 1 & 2:
Pollution Degree 3 & 4:
(See page 66
for descriptions of each pollution degree rating.)
All enclosures acceptable.
Enclosure that meets or exceeds IP54, NEMA/UL Type 12 required.
Category Specification