Rockwell Automation Publication 750-TD001H-EN-P - June 2013 37
PowerFlex 750-Series AC Drives
Fusing
The recommended fuse types are listed below. If available current ratings do not match those listed in the tables provided,
choose the next higher fuse rating.
• IEC – BS88 (British Standard) Parts 1 & 2, EN60269-1, Parts 1 & 2
(1)
, type gG or equivalent should be used.
• UL – UL Class CC, T, RK1, J, or L should be used.
Circuit Breakers
The “non-fuse” listings in the following tables include inverse time circuit breakers, instantaneous trip circuit breakers
(motor circuit protectors) and 140M self-protected combination motor controllers. If one of these is chosen as the desired
protection method, the following requirements apply:
• IEC – Both types of circuit breakers and 140M self-protected combination motor controllers are acceptable for IEC
installations.
• UL - Only inverse time circuit breakers and the specified 140M self-protected combination motor controllers are
acceptable for UL installations.
(1) Typical designations include, but may not be limited to the following; Parts 1 & 2: AC, AD, BC, BD, CD, DD, ED, EFS, EF, FF, FG, GF, GG, GH.