Housing width 22.5 mm Housing width 22.5 mm Housing width 22.5 mm Housing width 22.5 mm Housing width 22.5 mm
Technical data Technical data
Analog input RAD-IN-4A-I RAD-OUT-4A-I RAD-IN-8D RAD-OUT-8D-REL
Number of inputs 4 - - - 1 - -
Signal range 4 mA ... 20 mA - - - 4 mA ... 20 mA - -
Input resistance < 170 - - - < 170
Digital input
Number of inputs - - 8 - 2 2 -
Signal range - - 5 V AC/DC ... 30 V AC/DC - 5 V AC/DC ... 30 V AC/DC 0.1 V AC/DC ... 30 V AC/DC -
Switching level 1 signal (“H”) - - min. 5 V DC - min. 5 V DC (Common mode 3.6 V DC) / (differential mode 100 mV
0 signal (“L”) - - max. 1.5 V DC - max. 1.5 V DC - -
Input frequency max. 1 Hz
Pulse length - - - - - (High time 50
Analog output
Number of outputs - 4 - - 1 - -
Signal range - - - - 4 mA ... 20 mA - -
Load R
B
-700 (at U
B
= 24 V,
R
B
= [U
B
-10 V] / 20 mA)
-- 700
Digital output
Contact type - - - 8 x relay output 2 x relay output - Transistor output, passive
Switching voltage - - - 30 V AC/DC (EC Declaration of
Conformity)
30 V DC (with UL approval)
250 V AC (with UL approval)
Switching current - - - 0.5 A (EC Declaration of Confor-
mity)
2 A (with UL approval)
Clock frequency - - - - - - (High Speed 10 kHz with 50% Duty Cycle)
Frequency output - - - - - - (0.1 Hz ... 10 kHz (50% Duty Cycle))
General data
Supply voltage 9 V DC ... 30 V DC (via bus foot) 9 V DC ... 30 V DC (via bus foot) 9 V DC ... 30 V DC (via bus foot) 9 V DC ... 30 V DC (via bus foot) 9 V DC ... 30 V DC (via bus foot) 9 V DC ... 30 V DC (via bus foot) 9 V DC ... 30 V DC (via bus foot)
Current consumption Typ./max. 100 mA / 130 mA 100 mA / 130 mA 25 mA / 30 mA 100 mA / 160 mA 70 mA / 110 mA 35 mA / 45 mA 90 mA / 115 mA
Degree of protection IP20 IP20 IP20 IP20 IP20 IP20 IP20
Ambient temperature range -20 °C ... 65 °C -20 °C ... 65 °C -20 °C ... 65 °C -20 °C ... 65 °C -20 °C ... 65 °C -20 °C ... 65 °C -20 °C
Housing material Polyamide PA non-reinforced Polyamide PA non-reinforced Polyamide PA non-reinforced Polyamide PA non-reinforced Pol
Dimensions W / H / D 22.5 / 99 / 114.5 mm 22.5 / 99 / 114.5 mm
Conformance / approvals
Conformance CE-compliant CE-compliant
ATEX II 3 G EEx nL IIC II 3 G EEx nL IIC
IECEx Ex nL IIC Ex nL IIC
UL, USA / Canada Class I, Div. 2, Groups A, B, C, D Class I, Div. 2, Groups A, B, C, D Class I, Div. 2, Groups A, B, C, D Class I,
Ordering data Ordering data
Description Type Order No.
Pcs. /
Pkt.
Type Order No.
Pcs. /
Pkt.
Extension module Analog IN RAD-IN-4A-I 2867115 1
Extension module Analog OUT RAD-OUT-4A-I 2867128 1
Extension module Digital IN RAD-IN-8D 2867144 1
Extension module Digital OUT RAD-OUT-8D-REL 2867157 1
Extension module Mixed I/O
472 PHOENIX CONTACT
RAD-Line extension modules provide ad-
ditional inputs and outputs for bi-directional
RAD-Line IO and RAD-Line serial wireless
systems.
Easily installed via an integrated bus foot
Bus provides power supply voltage
Data transferred to transceiver module
via bus
Up to 8 modules can be connected to a
single transceiver
A maximum of 33analog or 66digital sig-
nals can be configured, depending on the
selection of modules
Extension modules
Industrial communication technology
Wireless data communication (900 MHz)
Analog components for
4 inputs or 4 outputs
Digital components for
8 inputs or 8 outputs
D
W
H
D
W
H
Vista de pagina 24
1 2 ... 20 21 22 23 24 25 26 27 28 29 30

Comentarios a estos manuales

Sin comentarios