Ex:
Housing width 52 mm
Technical data
Wireless path
Direction Bi-directional
Frequency range 902 MHz ... 928 MHz
Transmission power 10 ... 30 dBm
Serial port RS-232 RS-485
Connection method 9-pos. D-SUB (socket) COMBICON plug-in screw ter-
minal block
Serial transmission speed 300 ... 57,6 kbps
Data format/coding Asynchronous
Data flow control/protocols RTS/CTS
General data
Supply voltage 11 V DC ... 30 V DC
Current consumption 250 mA (at 24 V DC)
Degree of protection IP20
Ambient temperature range -40 °C ... 65 °C
Housing material Polyamide PA non-reinforced with aluminum heatsink
Dimensions W / H / D 52 / 99 / 115 mm
Screw connection solid/stranded/AWG 0.2 ... 4 mm² / 0.2 ... 2.5 mm² / 24 - 14
Conformance / approvals
Conformance FCC Directive, Part 15.247
ISC Directive RSS 210
UL, USA / Canada Class I, Div. 2, Groups A, B, C, D
Ordering data
Description Type Order No.
Pcs. /
Pkt.
Wireless module with optional Ethernet and serial interfaces
Bus foot for I/O extension modules RAD-ISM-900-EN-BD-BUS 2900017 1
Cannot be extended RAD-ISM-900-EN-BD 2900016 1
Wthout serial ports RAD-ISM-900-EN-BD/B 2901205 1
470 PHOENIX CONTACT
The RAD-ISM-900-EN-BD... industrial
wireless radio allows a wireless connection
of several decentralized controllers to a
central location (controller) via an Ethernet
or serial connection.
– Operates in the license-free 902-
928MHz ISM band
– Frequency-hopping spread spectrum
technology
– Provides an interface for transfer of data
between 900MHz wireless and Ethernet,
RS-232, RS-422 or RS-485 interfaces
– Contains an adjustable 10mW... 1 W
transmitter
– Supports TCP/IP, UDP and IP v4 proto-
cols
– Programmable for point-to-point, point-
to-multipoint and multipoint-to-point
configurations
– Incorporates security using selectable
128/192/256-bit AES encryption
– RAD-ISM-900-EN-BD-BUS features
an integrated bus foot to connect I/O
modules (addressable via Modbus)
– Individual modules can be configured as
master, slave or repeater using integrated
web browser interface
– RAD-ISM-900-EN-BD/B is a dedicated
slave radio with no Ethernet ports
Notes:
The products are offered exclusively for export outside the Euro-
pean Economic Area (EEA).
RAD-Line Ethernet
with Trusted Wireless
Industrial communication technology
Wireless data communication (900 MHz)
Wireless transceiver for Ethernet
and serial interfaces V.24
(RS-232, RS-422/RS-485)
Comentarios a estos manuales